I have a 14 Amp Ryobi miter saw. In the manual it has a table for required AWG by Cord Length and Amps. For 100’ and 12.1-16.0 Amps it just has a dash indicating there is no suitable AWG extension cable for this length and amp combination.

However, protoolreviews indicates 12 AWG is sufficient for 15 Amps and 100’, but 10 AWG would be safer. https://www.protoolreviews.com/extension-cord-size-chart-wire-gauge-amps/

Is protoolreviews correct and I can get away with a 10 AWG, 100’ extension cord for my 14 Amp tool just fine?

I know if something goes wrong it will likely be on me as Ryobi will point out I didn’t follow the manual.

  • Gypsyhermit123@lemmy.ca
    link
    fedilink
    English
    arrow-up
    4
    ·
    1 year ago

    Check your line voltage at your house. There is a lot of variance in house voltage. 110-125vac. Motors draw a minimum current and increases with load. your rating is for max load. So if you plan on a lot of deep cuts you might struggle. Smaller cuts will draw less.

    Long story short 10awg should be good.

    From southwire voltage calculator Results for Minumum Conductor Size Calculation 1 conductor per phase utilizing a 10 AWG copper conductor installed Cable, Conduit (non-Steel), & Direct Burial will limit the voltage drop to 2.45% or less when supplying 14 amps for 100 feet on a 120 volt single phase system.

    https://www.southwire.com/ca/en-ca/calculator-vdrop

    Nema motors are designed to work at the low range of 100v

    Nema quote

    An electric motor is electrically designed around the expected supply voltage with a tolerance. With NEMA (National Electrical Manufacturers Association) designs for small- and medium-voltage electric motors is +/- 10% voltage-maximum, with an allowable +/-5% frequency variation (ref.Jan 12, 2020

    https://theramreview.com/understanding-voltage-variations-and-electric-motors/#:~:text=An electric motor is electrically,5%25 frequency variation (ref.

  • Hazdaz@lemmy.world
    link
    fedilink
    English
    arrow-up
    3
    arrow-down
    1
    ·
    1 year ago

    How much cutting are you actually going to be doing? This is going to be key. The resistance on a smaller wire (larger gage number) and longer length is going to turn the cord hot. But if you’re making 3 cuts, I wouldn’t worry about it. If you are going to run it 24/7, then I’d worry.

    • mosher@lemm.eeOP
      link
      fedilink
      English
      arrow-up
      2
      ·
      1 year ago

      I’ll definitely be using it lightly. If I was cutting 24/7 I wouldn’t have gotten a Ryobi.

      • Hazdaz@lemmy.world
        link
        fedilink
        English
        arrow-up
        1
        arrow-down
        1
        ·
        1 year ago

        Run it for a few days at the expected use amount and keep an eye on the heat of the cord but also the outlet and plug. I do have to say that 100’ is a lot. No outlets closer than that to you?